TransWikia.com

GFCI for electric floor heat

Home Improvement Asked by gphil on May 11, 2021

I am installing electric floor heat in my bathroom. It will be on a dedicated 120V/20amp circuit. The breaker has a GFCI. I am using same manufacturer for thermostat as floor heat. The thermostat is a 120 Volt stat that is connected to the line and load. . The thermostat includes a integral GFCI. The thermostat’s GFCI has a end-of-life feature to isolate the heating cable load. Question: Should I keep the system with 2 GFCI’s or should I replace the breaker GFCI with a regular breaker? I can’t disable the thermostats GFCI.

One Answer

I would not put a GFCI breaker on this device. Code requires it to be GFCI protected and 2 GFCI devices can cause trouble in resetting.

I ran into a issue with one of the floor style that ran a self test that would trip the breaker so we could never reset it (the home owner called me I megged the heater and it was good so then I pulled 1 lead to the heater still tripped the panel breaker, called the mfg and they told me it was in there GFCI test that was tripping the circuit. I believe this test was the end of life test where it basically megged the circuit prior to energizing looking for leakage that may not show up on a standard test until wet.

Answered by Ed Beal on May 11, 2021

Add your own answers!

Ask a Question

Get help from others!

© 2024 TransWikia.com. All rights reserved. Sites we Love: PCI Database, UKBizDB, Menu Kuliner, Sharing RPP