TransWikia.com

How should I set my furnace's DIP switches to allow thermostatic control of the fan's stages?

Home Improvement Asked by Temp Star on April 6, 2021

I have a 16 year old Tempstar condensing 90+ two stage with variable speed motor. I just connected a Lyric T5 thermostat and would like to have the thermostat control the staging rather than the furnace. The manual says the 4th DIP switch on the control board must be in the ON position for two-stage thermostat operation. At present only the 2nd and 3rd are in the ON position. If I move the 4th to the ON position do the 1st, 2nd and 3rd stay in their present positions? Are any other adjustments required other than the wiring?

Thank you!

One Answer

It turns out that it is indeed the DIP switch location and moving the 4th one to the left (the ON position) is the factory setting of 1 OFF, 2 ON, 3 ON, 4 ON. No other adjustments other than to the wiring between the thermostat and the furnace were required.

Answered by Temp Star on April 6, 2021

Add your own answers!

Ask a Question

Get help from others!

© 2024 TransWikia.com. All rights reserved. Sites we Love: PCI Database, UKBizDB, Menu Kuliner, Sharing RPP